Potential implications of the amendments of Approved Document B on the cost of the services | ||
ºÚ¶´ÉçÇø type | Amendment | Indicative cost |
1 & 2 Blocks of flats | Provision of ventilation systems for the smoke control of common escape routes; | Based on a 10-floor development |
Ìý | Natural ventilation system comprising automatically opening vents | £2000 per floor per core |
Ìý | Or mechanically pressurised system | £8000 per floor per core |
3 Blocks of flats | Provide sprinkler protection to blocks of flats over 30 m high (to flats only, not common areas) | £17-23/m2 on the GIA |
Ìý | Ìý | Depends on the building height and the need for intermediate pumps and tank |
4 Residential care homes | Provision of free swing closing devices on bedroom doors (based on one bed per bedroom) | £150-200/door |
Ìý | Or provision of sprinkler protection in residential care homes with more than one bed per bedroom | £15/m2 on the GIA |
5 Offices, shop and commercial, assembly and recreation | Include for: Warning people with impaired hearing, Emergency voice communication to allow evacuation of people waiting in refuges | This brings the document in line with other regulations, so on the basis that these are being provided, it is assumed there is no additional cost |
6 Assembly and recreation | Provide for fire-fighting shafts in buildings between 7.5-18 m in height (fire-fighting lifts not required in shafts) | Ìý |
Ìý | Dry riser | £1500 per landing per core |
Ìý | Natural ventilation system comprising a system of automatically opening vents | £2000 per floor per core |
Ìý | Or mechanically pressurised system | £8000 per floor per core |
7 Storage | Remove provision for fire-fighting shafts in buildings between 7.5-18 m in height (assume no fire-fighting lifts in shafts) | Ìý |
Ìý | Omit dry riser | £1500 per landing per core |
Ìý | Omit natural ventilation system comprising a system of automatically opening vents | £2000 per floor per core |
Ìý | Or omit mechanically pressurised system | £8000 per floor per core |
8 Industrial/Storage | A maximum unsprinklered compartment size for a single-storey warehouse of 20,000 m² and/or 18 m high | £25-40/m2 for sprinkler system |
Ìý | Ìý | Depends on whether racking protection is required |
9 Self storage | A maximum unsprinklered compartment size of 2000 m² | £25-35/m² for sprinkler system |
Ìý | Ìý | Depends on degree of cellurisation |
10 All buildings other than dwelling houses | Discount an escape stair in buildings over 45 m with phased evacuation. Allowance for additional stair; | Ìý |
Ìý | Mechanical stair pressurisation ventilation system | £8000 per floor per core |
Ìý | Assume wet riser | £2000-4500 per landing per core |
Ìý | Ìý | Depends on the building height and the need for intermediate pumps, tank and valving |
11 All building other than dwelling houses | Provision of rising mains in escape stairs in all unsprinklered buildings over 30m tall in order to meet maximum distances from a fire main outlet | Ìý |
Ìý | Dry riser | £1500 per landing per core |
12 All buildings | Provision of cavity barriers in floor voids | This brings the document in line with other regulations so on the basis that these are being provided, it is assumed there is no additional cost |