Table 1: Fire survival time of for cables | ||
ºÚ¶´ÉçÇø service application | Performance objective | Fire survival time |
Fire fighting smoke control | Fire fighting | 2 hours |
Smoke control phased evacuation | Life safety | 1 hour |
Smoke control single stage evacuation | Life safety | ½ hour |
Smoke control dampers | Fire fighting | 2 hours |
Ìý | Life safety | 1 hour |
Table 2: Performance recommendation for fire-rated cable circuits | ||
ºÚ¶´ÉçÇø service application | Performance objective | Suggested cable Fire survival time |
CCTV single stage evacuation | Life safety | ½ hour |
CCTV phased evacuation | Life safety | 1 hour |
Central battery emergency lighting | Fire fighting | 2 hours |
Central battery escape lighting | Life safety | 1 hour |
Disabled evacuation communications | Life safety | ½ hour |
Way finding phased evacuation | Life safety | 1 hour |
Way finding single stage evacuation | Life safety | ½ hour |
Distribution mains for emergency | Life safety | ½ hour |
systems & escape lighting | Fire fighting | 2 hours |
Fire alarm activation devices phased evacuation | Life safety | 1 hour |
Fire alarm activation single phase evacuation | Life safety | ½ hour |
Fire alarm activation devices staged evacuation | Life safety | 1 hour |
Gaseous fire suppression systems single stage evacuation | Life safety | ½ hour |
Gaseous fire suppression systems phased evacuation | Life safety | 1 hour |
Phased fire alarm | Life safety | 2 hours |
Single phase fire alarm | Life safety | ½ hour |
Staged fire alarm | Life safety | 1 hour |
Systems monitoring and control for services in fire control centres | Fire fighting | 2 hours |
Fire-fighting lifts and associated electrical circuits including lighting, communications | Fire fighting | 2 hours |
Evacuation lifts | Life safety | ½ hour |
Sprinkler pumps | Fire fighting | 2 hours |
Wet risers | Fire fighting | 2 hours |