TABLE 1: Uptime Institute definitions of tier levels | ||||
Ìý | Tier I | Tier II | Tier III | TierIV |
Number of delivery paths | Only 1 | Only 1 | 1 Active, 1 Passive | 2 Active |
Redundancy | N | N+1 | N+1 | S+S or 2(N+1) |
Compartmentalisation | No | No | No | Yes |
Concurrently maintainable | No | No | Yes | Yes |
Fault tolerance to worst event | None | None | None | Yes |
TABLE 2: The tier attributes of the sites from which the actual availability numbers were drawn | ||||
Ìý | Tier I | Tier II | Tier II | Tier IV |
ºÚ¶´ÉçÇø type | Tenant | Tenant | Stand-alone | Stand-alone |
Staffing | None | 1 Shift | 1 + Shifts | %2224 by Forever%22 |
Useable for critical load | 100% N | 100% N | 90% N | 90% N |
initial gross watts per square foot (W/ft²) (typical) | 20-30 | 40-50 | 40-60 | 50-80 |
Ultimate gross W/ft² (typical) | 20-30 | 40-50 | 100-150 ¹ ² ³ | 150+ ¹ ² |
Uninterruptible cooling | None | None | Maybe | Yes |
Support space to raised-floor ratio | 20% | 30% | 80-90%² | 100+% |
Raised-floor height (typical) | 12%22 | 18%22 | 30-35%22² | 30-36%22² |
Floor loading ibs/ft² (typical) | 85 | 100 | 150 | 150 |
Utility voltage (typical) | 208,480 | 208, 480 | 12-15 kV² | 12-15 kV² |
Single points-of failure | Many + human error | Many + human errors | Some + human error | None + human error |
Annual site-caused IT downtime (actuals) | 28.8 hours | 22.0 hours | 1.6 hours | 0.4 hours |
Site availablity | 99.671% | 99.749% | 99.982% | 100.00% |
Months to implement | 3 | 3-6 | 15-20 | 15-20 |
Year first deployed | 1965 | 1970 | 1985 | 1995 |
Construction cost (:30%)¹²³ | Ìý | Ìý | Ìý | Ìý |
Raised floor | $220/´Ú³Ù² | $220/´Ú³Ù² | $220/´Ú³Ù² | $220/´Ú³Ù² |
Useable UPS output | $10,000/kW | $11,000/kW | $20,000/kW | $22,000/kW |
³ 100 W/ft² maximum for air-cooling over large areas, water or alternate cooling methods greater than 100 W/ft² (added costs excluded). | ||||
² Greater W/ft² densities require greater support space (100% at 100 W/ft² and up to 2 or more times at greater densities), higher raised floor, and if required over large areas, medium voltage service entrance. | ||||
¹ Excludes large architectural, engineering, and commissioning fees; permits and other fees; interest; and abnormal civil costs. These can be several million dollars. Assumes minimum of 15,000 ft² of raised floor. Architecturally plain one-story building, with power backbone sized to achieve ultimate capacity with installation of additional components or systems. Make adjustments for NYC, Chicago, and other high cost areas. |
TABLE 3: Comparison of Various UPS Systems | |||||
Specification | 6 Pulse Series Online | 12 Pulse Series Online | Parallel Online | Hybrid Rotary | Diesel Rotary UPS |
Typical Operating Efficiency | 94% | 94% | 96% | 90 - 95% | 90 - 96% |
Input Power Factor | 0.8 | 0.85 | 0.99 | 0.98 | 0.99 |
Output Voltage Regulation | Yes | Yes | Yes | Yes | Yes |
Input Power Factor Correction | No | No | Yes | Yes | Yes |
Energy Store | Battery | Battery or DC Flywheel | Battery | Battery or DC Flywheel | AC Flywheel |
Output Fault Current Without Mains Available | Up to 2.2Ìýx In | Up to 2.2Ìý x In | Up to 2.2Ìýx In | 14 x In | 10 - 12 x In |
Range of sizes to Largest Unit Size | 0 – 800ÌýkVA | 0 – 800ÌýkVA | 500 kVA | 180 -1100ÌýkVA | 2 MVA |
Actual useful size allowing for derating for leading Power Factor | 640 KVA | 640 KVA | 400 KVA | 1100ÌýKVA | 2 MVA |
Indicative cost of UPS Only (£/kVA) | £180 - £200 | £180 - £200 | £180 - £200 | £245 - £265 | N/A |
Indicative Cost of UPS if derated to allow for leading power factors (£/kVA) | £225 -£250 | £225 -£250 | £225 -£250 | £245 - £265 | N/A |
Indicative cost of UPS in £/kVA on N+1 basis at most optimum module size | TBC | TBC | TBC | TBC | TBC |
Indicative cost of UPS and Standby Generation (£/kVA) | £405 -£435 | £405 -£435 | £405 -£435 | £440 - £470 | £450 -£480 |
Indicative cost of UPS and Standby Generation if UPS derated to allow for leading power factors (£/kva) | £450 -£485 | £450 -£485 | £450 - £485 | £440 - £470 | £450 -£480 |
Indicative Space Requirement of UPS and standby generation (m²/kVA) | 0.06 -0.07 | 0.06 -0.07 | 0.06 -0.07 | 0.06 - 0.07 | 0.04 -0.05 |