Labour time comparison for Cablofil against traditional tray | |||||
Ìý | Ìý | Traditional installation | Ìý | Cablofil installation | Ìý |
Ìý | Ìý | Time per | Total | Time per | Total |
Ìý | Ìý | unit (hrs) | (hrs) | unit (hrs) | (hrs) |
900 mm HD ladder | 120 m | 1.583 | 189.96 | 0.74 | 88.8 |
Brackets | 80 | 0.75 | 80 | 0.75 | 80 |
90° bend | 3 | 1.033 | 3.099 | 0.96 | 2.88 |
45° bend | 1 | 1.033 | 1.033 | 0.96 | 0.96 |
Tee | 4 | 1.333 | 5.332 | 1 | 4 |
Crossover | 0 | 1.5 | 0 | 1 | 0 |
450 mm HD tray | 120 m | 0.566 | 67.92 | 0.368 | 44.16 |
Brackets | 80 | 0.5 | 40 | 0.5 | 40 |
90° bends | 3 | 0.533 | 1.599 | 0.48 | 1.44 |
45° bends | 1 | 0.533 | 0.533 | 0.48 | 0.48 |
Tee | 4 | 0.766 | 3.064 | 0.75 | 3 |
600 mm HD 3c tray | 120 m | 0.8 | 96 | 0.48 | 57.6 |
Brackets | 80 | 0.6 | 48 | 0.6 | 48 |
90° bends | 3 | 0.666 | 1.998 | 0.58 | 1.74 |
45° bends | 1 | 0.666 | 0.666 | 0.58 | 0.58 |
Tee | 4 | 1.1 | 4.4 | 0.85 | 3.4 |
CF54300 wire tray | 120 m | 0.249 | 29.88 | 0.249 | 29.88 |
Brackets | 80 | 0.333 | 26.64 | 0.333 | 26.64 |
90° bends | 3 | 0.284 | 0.852 | 0.284 | 0.852 |
45° bends | 1 | 0.284 | 0.284 | 0.284 | 0.284 |
Tee | 4 | 0.366 | 1.464 | 0.366 | 1.464 |
Ìý | Total | Ìý | 602.724 | Ìý | 436.16 |
Information provided for cost analysis on a shopping centre project (December 2005) |
Site powered by